BMED
Single-phase isolating transformers for supplying rooms used for medical purposes
3 - 10 kVA

General design features:
  • Input voltage AC 230 V
  • Output voltage AC 230 V (with center tap)
  • Low-loss design with grain-oriented M165-35S sheet metal
  • maximum open-circuit voltage AC 250V between the outer conductors
  • No-load current maximum 3% Inenn
  • Short-circuit voltage Uk maximum 3%
  • Inrush current maximum 12x Inenn
  • Reinforced insulation and insulated shielding foil between the windings
  • Structurally insulated mounting brackets
  • Temperature monitoring with PTC thermistor 120°C in each coil
  • Shield winding with insulated connection led out
  • Back of hand and finger touch-proof clamps in accordance with DGUV regulation 3
  • IP xx B, insulation class E, max. ambient temperature 40°C (ta 40°C/E)
  • Vacuum impregnation
  • Overload protection is not permitted, only short-circuit protection
  • Other voltages, outputs or versions on request

Standards:

EN 61558-2-15
Transformers for rooms used for medical purposes

Certificates and standards Single-phase motor

Type Art. No. Power
[kVA]
Size Copper
[kg]
Total
[kg]
Dimensions [mm]
B T H a b Screw
BMED 3000 0545-10-003000 3 UI 150/77 12,8 31 195 147 330 124 139 M8
BMED 4000 0545-10-004000 4 UI 150/92 14,1 35 195 165 330 124 154 M8
BMED 5000 0545-10-005000 5 UI 150/103 16,8 40 195 176 330 124 165 M8
BMED 6300 0545-10-006300 6,3 UI 180/78 22,1 46 236 168 370 144 160 M8
BMED 8000 0545-10-008000 8 UI 210/63 32,0 59 280 163 430 176 153 M10
BMED 10000 0545-10-010000 10 UI 210/88 39,9 78 280 188 430 176 178 M10

 