BSE
CONTROL TRANSFORMERS,
COST-OPTIMIZED

50 – 800 VA

General design features:

  • control transformer with standard voltages
  • cost-optimized
  • welded
  • Voltage adjustment through 230V/400V tapping on the input side
  • open version for stationary installation
  • hand-back and finger-touch-proof terminals, according to DGUV regulation 3 (IPxxB)
  • IP xx B, insulation class B, max. ambient temperature 40°C (ta 40°C/B)
  • 50-250 VA version with combined DIN mounting plate

Standard voltages:

AC 230/400V // AC 24V
AC 230/400V // AC 230V

Standards:

EN 61558-2-2
Control transformers
EN 61558-2-4
Isolating transformers
EN 61558-2-6
Safety transformers

 

Type Power
[VA]
230/400 // 24 V
Art. Nr.
230/400 // 230 V
Art. Nr.
BSE 50 50 0536-10-000050 0537-10-000050
BSE 100 100 0536-10-000100 0537-10-000100
BSE 160 160 0536-10-000160 0537-10-000160
BSE 250 250 0536-10-000250 0537-10-000250
BSE 400 400 0536-10-000400 0537-10-000400
BSE 630 630 0536-10-000630 0537-10-000630
BSE 800 800 0536-10-000800 0537-10-000800

 

Type Size Copper
[kg]
Total
[kg]
Dimensions [mm]
B T H a b Schraube
BSE 50 EI 66/36 0,16 0,98 78 80 83 56 56 M4 / HS
BSE 100 EI 84/43 0,24 1,68 85 82 93 64 65 M4 / HS
BSE 160 EI 84/52 0,39 2,30 85 98 97 64 65 M4 / HS
BSE 250 EI 96/59 0,58 3,70 96 102 104 84 87 M5 / HS
BSE 400 EI 120/53 1,02 5,20 120 100 120 90 82 M5
BSE 630 EI 135/62 1,66 6,90 135 115 131 104 96 M5
BSE 800 EI 150N/66 1,73 9,30 150 124 145 122 101 M6

 

Product details of the BSE single-phase control transformers

Breimer-Roth GmbH produces single-phase control transformers according to DIN EN 61558-2-2 in various standard voltages. The input voltage can be adapted to the respective mains voltage by means of the 230V/400V tapping provided. The terminals for the input and output voltage are back-of-hand and finger-touch-proof in accordance with DGUV regulation 3. With a power rating of 50 VA – 250 VA, a combined mounting of the transformer is possible using top-hat rail mounting. The mandatory use of control transformers is regulated in DIN VDE 0113 Part 1.
Our control transformers are manufactured as single-phase transformers with separate windings – galvanic isolation – and fixed voltage combinations and can be used in the frequency range of 50 Hz and 60 Hz.
The maximum single-phase power of the BSE series is 800VA

Advantages of the BSE single-phase control transformers from Breimer-Roth GmbH

Our control transformers are cost-optimised transformers. Insulation class B at an ambient temperature of 40° C is standard for all control transformers in the BSE series.

Application areas of the BSE single-phase control transformer

The transformers in the BSE series are single-phase transformers with an input voltage of 230 V or 400 V and output voltages of 230 V or 24 V for supplying control and regulation devices. Due to the different power grids worldwide, which are often operated without a centre conductor, a control voltage cannot be provided. Control transformers have a low voltage drop with an inductive load. According to DIN VDE 0113 Part 1, a control transformer must be provided in electrical systems if machines and systems have more than five electromagnetic actuating coils, relays and contactors, if control and regulating devices are installed outside control cabinets and machines or if electronic control or signalling circuits are to be fed

SIE HABEN FRAGEN?

LASSEN SIE UNS SPRECHEN!

ODER NUTZEN SIE UNSER KONTAKTFORMULAR!

Für konkrete anfragen nutzen sie bitte unser detailliertes anfrageformular