BDMED
Three-phase isolating transformers supplying medical rooms
3 - 10 kVA

General design features:
  • Input voltage 3AC 400 V
  • Output voltage 3AC 230 V
  • Low-loss design with grain-oriented M165-35S sheet metal
  • maximum open-circuit voltage AC 250V between the outer conductors
  • No-load current maximum 3% Inenn
  • Short-circuit voltage Uk maximum 3%
  • Inrush current maximum 12x Inenn
  • Reinforced insulation and insulated shielding foil between the windings
  • Structurally insulated mounting brackets
  • Temperature monitoring with PTC thermistor 120°C in each coil
  • Shield winding with insulated connection led out
  • YNyn0 shift group
  • Back of hand and finger touch-proof clamps in accordance with DGUV regulation 3
  • IP xx B, insulation class E, max. ambient temperature 40°C (ta 40°C/E)
  • Vacuum impregnation
  • Other voltages, outputs or versions on request

Standards:

EN 61558-2-15
Transformers for rooms used for medical purposes

Certificates and standards Three-phase transformers

Type Art. No. Power
[VA]
Size Copper
[kg]
Total
[kg]
Dimensions [mm]
B T H a b Screw
BDMED 3000 0618-10-003000 3 3UI 150/77 15,2 45,5 300 165 330 224 140 M8
BDMED 4000 0618-10-004000 4 3UI 150/92 18,6 52,0 300 180 330 224 154 M8
BDMED 5000 0618-10-005000 5 3UI 150/103 19,7 56,0 300 191 330 224 165 M8
BDMED 6300 0618-10-006300 6,3 3UI 180/63 27,6 63,0 360 165 380 264 145 M8
BDMED 8000 0618-10-008000 8 3UI 210/63 37,4 85,0 420 170 430 316 153 M10
BDMED 10000 0618-10-010000 10 3UI 210/73 39,1 89,0 420 180 430 316 163 M10