BDMED
THREE-PHASE ISOLATING TRANSFORMER FOR SUPPLY OF MEDICAL ROOMS
3 – 10 kVA

General design features:

  • Input voltage 3AC 400 V
  • Output voltage 3AC 230 V
  • Low-loss version with grain-oriented M165-35S metal sheet
  • Maximum open circuit voltage AC 250 V between the outer conductors
  • No-load current max. 3% of nominal current
  • Short-circuit voltage UK maximum 3%
  • Inrush current maximum 12x nominal current
  • Reinforced insulation and insulated shielding foil between the windings
  • Structurally insulated mounting brackets
  • Temperature monitoring with thermistor 120°C in each coil
  • Shield winding with led out, insulated connection
  • Switching group YNyn0
  • Hand-back and finger-touch-proof terminals according to DGUV regulation 3
  • IP xx B, isolation class E, max. ambient temperature 40°C (ta 40 °C/E)
  • Vacuum impregnation
  • Other voltages, powers or versions on request

Standards:


EN 61558-2-15

Transformers for medical use



Certificate and standards of three-phase transformers

TypeArt. No.Power
[VA]
SizeCopper
[kg]
Total
[kg]
Dimensions [mm]
BTHabScrew
BDMED 30000618-10-00300033UI 150/7715,245,5300165330224140M8
BDMED 40000618-10-00400043UI 150/9218,652,0300180330224154M8
BDMED 50000618-10-00500053UI 150/10319,756,0300191330224165M8
BDMED 63000618-10-0063006,33UI 180/6327,663,0360165380264145M8
BDMED 80000618-10-00800083UI 210/6337,485,0420170430316153M10
BDMED 100000618-10-010000103UI 210/7339,189,0420180430316163M10