BOPL
SINGLE-PHASE ISOLATING TRANSFORMER
FOR SUPPLY OF SURGERY LIGHTS

100 – 1000 VA

General design features:

  • input voltage AC 230 V ±5% ±10%
  • output voltage AC 23/24/25/26/27/28 V
  • reinforced insulation and insulated shielding foil between the windings
  • structurally insulated mounting brackets
  • shield winding with lead out, insulated connection
  • hand-back and finger-touch-proof terminals, according to DGUV regulation 3 (IPxxB)
  • IP xx B, isolation class E, max. ambient temperature 40°C (ta 40°C/E)
  • other voltages, powers or designs on request

Standards:

EN 61558-2-6 Safety transformers

Certificate and standards single-phase transformers

Type Art. No. Power
[VA]
Output current
[A]
Size Copper weight
[kg]
Total weight
[kg]
Dimensions [mm]
B T H a b Screw
BOPL 100 0546-10-000100 100 3,57 EI 84/43 0,33 1,68 85 68 93 64 57 M4
BOPL 160 0546-10-000160 160 5,70 EI 96/45 0,45 2,95 96 88 104 84 80 M5
BOPL 270 0546-10-000270 270 9,64 EI 105/60 0,63 4,70 105 104 110 84 95 M5
BOPL 400 0546-10-000400 400 14,3 EI 120/61 1,00 6,20 120 108 120 90 100 M5
BOPL 630 0546-10-000630 630 22,5 EI 135/62 1,76 7,00 135 115 131 104 106 M5
BOPL 800 0546-10-000800 800 28,6 EI 150N/66 2,43 10,10 150 124 145 122 111 M6
BOPL 1000 0546-10-001000 1000 35,7 EI 150N/92 2,64 13,00 150 150 145 122 137 M6

 

SIE HABEN FRAGEN?

LASSEN SIE UNS SPRECHEN!

ODER NUTZEN SIE UNSER KONTAKTFORMULAR!

FĂĽr konkrete anfragen nutzen sie bitte unser detailliertes anfrageformular