BMED
SINGLE-PHASE ISOLATING TRANSFORMER
FOR SUPPLY OF MEDICAL ROOMS

3 – 10 kVA

General design features:

  • input voltage AC 230 V
  • output voltage AC 230 V (with center tap)
  • low-loss version with grain-oriented metal sheet M165-35S
  • maximum open circuit voltage AC 250 V between the outer conductors
  • no load current max. 3% inside
  • short-circuit voltage UK maximum 3%
  • inrush current maximum 12x inside
  • reinforced insulation and insulated screen foil between the windings
  • structurally insulated mounting brackets
  • temperature monitoring with thermistor 120°C in each coil
  • shield winding with lead out, insulated connection
  • hand-back and finger-touch-proof terminals, according to DGUV regulation 3 (IPxxB)
  • IP xx B, isolation class E, max. ambient temperature 40°C (ta 40°C/E)
  • vacuum impregnation
  • overload protection is not permitted; only short-circuit protection
  • other voltages, powers or versions on request

Standards:

EN 61558-2-15
Transformers for supply of medical rooms

Certificate and standards single-phase transformers

Type Art. No. Power
[kVA]
Size Copper weight
[kg]
Total weight
[kg]
Dimensions [mm]
B T H a b Screw
BMED 3000 0545-10-003000 3 UI 150/77 12,8 31 195 147 330 124 139 M8
BMED 4000 0545-10-004000 4 UI 150/92 14,1 35 195 165 330 124 154 M8
BMED 5000 0545-10-005000 5 UI 150/103 16,8 40 195 176 330 124 165 M8
BMED 6300 0545-10-006300 6,3 UI 180/78 22,1 46 236 168 370 144 160 M8
BMED 8000 0545-10-008000 8 UI 210/63 32,0 59 280 163 430 176 153 M10
BMED 10000 0545-10-010000 10 UI 210/88 39,9 78 280 188 430 176 178 M10

 

SIE HABEN FRAGEN?

LASSEN SIE UNS SPRECHEN!

ODER NUTZEN SIE UNSER KONTAKTFORMULAR!

Für konkrete anfragen nutzen sie bitte unser detailliertes anfrageformular