BMED
SINGLE-PHASE ISOLATING TRANSFORMER
FOR SUPPLY OF MEDICALLY USED ROOMS

3 – 10 kVA

General design features:

  • Input voltage AC 230 V
  • Output voltage AC 230 V (with center tap)
  • Low-loss version with grain-oriented M165-35S metal sheet
  • Maximum open circuit voltage AC 250 V between the outer conductors
  • No load current max. 3% inside
  • Short-circuit voltage UK maximum 3%
  • Inrush current maximum 12x inside
  • Reinforced insulation and insulated screen foil between the windings
  • Structurally insulated mounting brackets
  • Temperature monitoring with thermistor 120°C in each coil
  • Shield winding with lead out, insulated connection
  • Hand-back and finger-touch-proof terminals, according to DGUV regulation 3
  • IP xx B, isolation class E, max. ambient temperature 40°C (ta 40°C/E)
  • Vacuum impregnation
  • Overload protection is not permitted; only short-circuit protection
  • Other voltages, powers or versions on request

Standards:


EN 61558-2-15

Transformers for supply of medical rooms



Certificate and standards single-phase transformers

TypeArt. No.Power
[kVA]
SizeCopper
[kg]
Total
[kg]
Dimensions [mm]
BTHabScrew
BMED 30000545-10-0030003UI 150/7712,831195147330124139M8
BMED 40000545-10-0040004UI 150/9214,135195165330124154M8
BMED 50000545-10-0050005UI 150/10316,840195176330124165M8
BMED 63000545-10-0063006,3UI 180/7822,146236168370144160M8
BMED 80000545-10-0080008UI 210/6332,059280163430176153M10
BMED 100000545-10-01000010UI 210/8839,978280188430176178M10